Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00252
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2012 | ELECTRIC - FINAL | Approved | ||
01/11/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* EQUIPMENT FOR LISTING: 1) AIR FLOW UNITS, BANDSAW, DYNOMETER AND BUS LIFT IN WASH AREA 2) OK PAINT BOOTH |
|
01/10/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH ITEMS 2, 3 AND 4 INSPECTION 01/05/12 & ITEM #6 INSPECTION 12/07/11 |
|
01/05/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) SUPPORT JUNCTION BOX FOR CORDS 2) USE APPROVED FITTING 3) CLEAN SURFACE UNDER GROUND BAR 250.12 4) PROPERLY INSTALL LOCK NUTS 5) PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
12/19/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WAITING ON VERIFICATION OF EQUIPMENT LISTINGS |
|
12/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL ALL ELECTRICAL EQUIPMENT 2) SEAL OFF OK TO SEAL 3) GROUNDED CONDUCTOR TO BE GRAY 277/480V 4) PLANS CALL FOR CONDUIT OUT OF HAZARDOUS ZONE-HAVE M/C CABLE 5) DOOR MOTOR INSIDE OF 3' RADIUS 6) BOND PER 250.97 7) REDUCING WASHERS IMPROPERLY INSTALLED 8) CHECK TOP OF UNIT AND ROOF NEXT TIME 9) A REFEE MAYBE ASSESED FOR INCOMPLETE INSPECTIONS |
|
12/05/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
11/29/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
11/15/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTHING CONNECTED TO TROLLY DISCONNECT 2) OK ROOM 267 |
|
11/10/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/07/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/01/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) DEDICATED WORKING SPACE BUS LIFT DISCONNECT, DYNO DISCO 110.26 2) PLEASE VERIFY DYNOMETER LISTING 3) CITY SPECS REQUIRE LISTING AND LABELING OF EQUIPMENT PAINT BOOTH: 1) BOND BUSHINGS 2??.97 2) INPROPERLY INSTALLED REDUCING WASHERS 3) USE ? M/C SUPPORTS 5) TIGHTEN LOOSE FITTINGS |
|
10/28/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/25/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/21/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOM #174-177 AND 155-157 |
|
10/20/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WILL NEED TO SEE EQUIPMENT AND CONNECTIONS 20 OK ROOM 253, 262, 259, 258, 265, 266 & 182 |