Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00252
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/07/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY BUS LIFT LISTING 2) VERIFY DYNO SEALING THRU WALL 3) PAINT BOOTH TO BE INSTALLED WIRING PER NEC-FINISH ALL ITEMS AND CHECK FOR OTHERS. TO MANY TO LIST |
|
11/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WILL WAIT FOR RICK HOLLANDER |
|
11/23/2011 | ELECTRIC - INTERMEDIATE | Denied | PAINT BOOTH: 1. VERIFY LISTING LABELS - BREATHER IS PER MEDICAL EQUIPMENT - MIXING ROOM IS IN ADDITION TO BOOTH. 2. CLEAN FOREIGN MATERIAL & DIRT FROM DISCONNECT 3. LABEL PANEL & COVER 408.4 - NEED OPEN FOR INSPECTION 4. NEED PLANS FOR EQUIPMENT 5. LABEL DISCONNECTS 6. INSTALL ALL STRANDS UNDER GROUND SCREW 7. LOOSE FITTINGS & HUBS 8. WIRING METHODS NOT SUPPORTED ON ROOF 9. NEED NRTL VERIFICATION OF UNIT |
|
11/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOF OVER 164 & 165 |
|
10/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK JUNCTION BOX IN ELECTRIC ROOM |
|
10/04/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK MTH8A, MTH8B, TMTL8A, MTHL8A, MTHL8B, AHU10 AND AHU11 |
|
09/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/21/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
09/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANELS MTH7A, MTH7B, TMTL7A, MTL7B, MTL6A AND MTL6B |
|
08/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/19/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK TO RE-ENERGIZE CUSTOMER SERVICE UNDER LO/TO RECEIVED CHECK 1687 FOR $165.00 OK TERMINATIONS AT BREAKER MTDSA, MESES A (ALL), BUILDING 5 PAD MOUNT, BREAKER MTH7A |
|
08/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WILL NEED LETTER OF TORQUE 2) REMOVE NEUTRAL BOND 250.24 3) NEED BOLTS BACK OF BREAKER SECTION OK MTDSA,MTHL AND MTL, EXCEPT AS NOTED |
|
08/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CHICO IN SEALS |
|
08/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO SEAL PIT WIRING PER MANUFACTURERS INSTRUCTIONS 2) FINISH POWER SEALS 3) OK SMOKE DETECTOR ROOM 186 |
|
08/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND LID ROOM 184 2) VERIFY CABLE IN SEAL OFF FOR EXCEPTION |
|
07/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 169, 172,173 AND 174 WEST |
|
06/30/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 170,171,172 AND 169 |
|
06/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOM 158-160 WALLS |
|
06/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTH WALL ROOM 158-160 |
|
06/07/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK #2 BARE ? NEZZINE 2) OK H3/0 BLDG STEEL TO BLDG STEEL ? DOOR 150 |
|
03/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FIRE STOPPING TO BE CHECKED BY BLDG INSPECTOR 2) OK CONDUCT WORK IN EXISTING PORTION OF BLDG 3) OK GROUNDING CONDUCTOR UNDER SLAB TO BLDG STEEL |
|
03/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/03/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |