Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/18/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/23/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSULATE LINEAR SLOT DIFFUSSER CANS. 2) GRID WIRE BLOCKING ACCESS AT V.A.N. 3) DIFFUSERS MISSING. 4) PROVIDE SPRINK INSULATORS ON IN LINE FAN. 5) INSTALL VOLUME DAMPERS IN SUPPLY DUCT. 6) INSULATE SUPPLY DUCT. |
|
| 06/23/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO MECH CONTRACTOR ON SITE NO CONTACT NUMBER |
|
| 03/29/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1ST AND 2ND FLOOR MED AND LOW RPESSURE 2) DUCT OK TO INSULATE |