Permit: T10CM00251

Parcel: 106101650


Addresses:

3910 N SUN TRAN BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00251

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2011 ELECTRIC - FINAL Approved LISTING INFORMATION FOR SHUTTERS AND DOORS ACCEPTED
12/08/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED EM LIGHTING TEST
2) OK GFCI'S
12/05/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS #3 10/21/11 AND 2 & 3 FROM 10/17/11 INSPECTIONS
11/29/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) WILL WAIT FOR RICK HOLLANDER
10/28/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/21/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL DOOR OPERTORS
2) FINISH PREVIOUS ITEMS
3) WILL NEED EMERGENCY LIGHTING TEST
10/19/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/17/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SUPPORT 'T' STAT RACEWAYS
2) VERIFY LISTING AND LABEL OF SHADE MOTORS PER PLANS
3) GFCI AH-2 NOT WORKING (ON UNIT)
4) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8
5) NEED TO SEE FURNITURE CONNECTIONS 605.5 & 7-WILL APPLY
6) FINISH PREVIOUS ITEMS 3 & 4
7) RECEIVED LETTERS OF TORQUE
10/14/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
10/12/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CLEANOUT FLOOR BOX
2) GROUND FLOOR BOX COVER
3) BOXES MORE THAN 1/4" 314.20
4) GFI WITHIN 6' OF A SINK