Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM00251
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2011 | ELECTRIC - FINAL | Approved | LISTING INFORMATION FOR SHUTTERS AND DOORS ACCEPTED | |
12/08/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEIVED EM LIGHTING TEST 2) OK GFCI'S |
|
12/05/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS #3 10/21/11 AND 2 & 3 FROM 10/17/11 INSPECTIONS |
|
11/29/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WILL WAIT FOR RICK HOLLANDER |
|
10/28/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/21/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL DOOR OPERTORS 2) FINISH PREVIOUS ITEMS 3) WILL NEED EMERGENCY LIGHTING TEST |
|
10/19/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/17/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SUPPORT 'T' STAT RACEWAYS 2) VERIFY LISTING AND LABEL OF SHADE MOTORS PER PLANS 3) GFCI AH-2 NOT WORKING (ON UNIT) 4) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8 5) NEED TO SEE FURNITURE CONNECTIONS 605.5 & 7-WILL APPLY 6) FINISH PREVIOUS ITEMS 3 & 4 7) RECEIVED LETTERS OF TORQUE |
|
10/14/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
10/12/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CLEANOUT FLOOR BOX 2) GROUND FLOOR BOX COVER 3) BOXES MORE THAN 1/4" 314.20 4) GFI WITHIN 6' OF A SINK |