Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2010 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 03/31/2010 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED BREAKER FOR TRANSFORMER 2) CANNOT STACK LUGS 3) GROUNDING ELECTRODE CONDUCTORS TO BE ON SAME LUG AS MAIN BONDING JUMPER FOR GROUNDED CONDUCTOR 4) FILL UNUSED CONDUIT OPENINGS 5) PANEL "PC" NOT MADE UP |