Permit: T10CM00217

Parcel: 128114080


Addresses:

4850 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/20/2010 PLUMBING - FINAL Approved PER INSP CARD
07/19/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/14/2010 PLUMBING - FINAL Partial Approval OK - TCO FOR MOVING EQUIPMENT ONLY
07/13/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) STERILIZATION AND BACTERIA REPORT ON SITE
2) COMPLETE INSTALLS OF VACUUM PUMP AND AIR COMPRESSOR PER APPROVED PLAN SEE DETAILS P1.2 WITH CORRECT TERMINATIONS AND LABELING
3) COMPLEE INSTALL OF OTHER EQUIPMENT OWNER PROVIDED
4) INSTALL DRINKING WATER DISPENSER
07/06/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/01/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) READ ALL NOTES AND COMPLY
2) CALL IN ALL INSPECTIONS ON PLUMBING PERMIT CARD
3) INSTALL ALL EQUIPMENT, PROVIDE STERILIZATION AND BACTERIA REPORT FOR POTABLE WATER SYSTEM
4) PROVIDE BACKFLOW PROTECTION ON ALL HAND SPRAYERS AT SINKS THAT HAVE VALVES
5) REPAIR ALL LEAKS AND LABEL ALL AIR AND VACUUM
6) INSTALL WATER HEATER PIPING PER PLAN (CHECK VALVE) AND INSULATE HOT & HOT RETURN
7) PROVIDE LISTING FOR SINK SUPPLY TUBING
8) PAINT ALL VENTS ON ROOF EXPOSED TO SUNLIGHT ? ? PLASTIC
9) BREAK OFF ALL HOSE BIB TAMPER SCREWS
10) LIST NOT COMPLETE