Permit: T10CM00216

Parcel: 136092110

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM00216

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/16/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE PANEL NOT LISTED TO HAVE SPLIT BREAKERS
2) #8 GROUNDING ELECTRODE CONDUCTOR TO RUN TO SEPERATELY DERIVED SYSTEMS (INVERTERS) WITHOUT SPLICE
3) INSTALL BONDING JUMPERS AROUND SPLICE PLATES ON URNIAL
4) GROUND ALL METAL RACEWAYS
5) INSTALL FLASHING ON ALL ROOF PENETRATIONS AND SEAL
6) MISSING COMBINER BOXES. A/C DISCONNECTS PER PLANS
7) INSTALL WARNING LABELS