Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/16/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE PANEL NOT LISTED TO HAVE SPLIT BREAKERS 2) #8 GROUNDING ELECTRODE CONDUCTOR TO RUN TO SEPERATELY DERIVED SYSTEMS (INVERTERS) WITHOUT SPLICE 3) INSTALL BONDING JUMPERS AROUND SPLICE PLATES ON URNIAL 4) GROUND ALL METAL RACEWAYS 5) INSTALL FLASHING ON ALL ROOF PENETRATIONS AND SEAL 6) MISSING COMBINER BOXES. A/C DISCONNECTS PER PLANS 7) INSTALL WARNING LABELS |