Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM00201
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) AC-1 BEYOND 10 PERCENT +/- PERIMETERS PROVIDE ENGINEERS APPROVAL ON CFM CHANGES 2) NO LIFE SAFETY ISSUES OBSERVED, SEE BLDG INSPECTOR FOR TEMP C OF O |
|
| 04/14/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BALANCE REPORT NOT COMPLETE |
|
| 04/09/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/06/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* NR BALANCE REPORT NOT ON SITE |
|
| 04/01/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST OK X 3 2) PROVIDE COMPLETE AIR BALANCE REPORT 3) NO LIFE SAFETY ISSUES OBSERVED, SEE BLDG INSPECTOR FOR TEMP C OF O |
|
| 03/31/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ENGINEER APPROVED BALANCE REPORT 2) PROVIDE DUCT SMOKE DETECTOR TEST, MECHANICAL CONTRACTOR TO BE ON SITE FOR TEST |