Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2010 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 05/17/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/13/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/06/2010 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PSI TEST NOT HOLDING 2) WEATHER RESISTANT SUPPORTS REQUIRED 3) WH PAN REQUIRED WITH WOOD SUPPORTING STRUCTURE 4) TYPE B VENT ABOVE ENCLOSURE 5) SEDIMENT TRAPS REQUIRED 6) CORRECT DRIPPING RELIEF VALVE, AND TERMINATE WITH OUT THREADS 7) TERMINATE CONDENSATE TO APPROVED LOCATION |
|
| 03/01/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/26/2010 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |