Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) BLDG LOCKED AND NO ONE ON SITE |
|
| 08/04/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE OPEN SPLICES OPEN BOXES AND UNSECURED LIGHT FIXTURES IN BACK AREA 2) NEED TO REVISE ONE LINE TO REFLECT HI/LEG SERVICE AND CHANGES IN FEEDERS FROM CU TO AL 3) NEED ACCESS TO ROOF 4) NEED SERVICE LABELING PER NEC 110.22 5) LABEL BREAKERS IN HOUSE PANEL AND PANEL 'C' 6) PLAN CALLS FOR EXHAUST FANS TO BE ON TIME CLOSCK SO FANS RUN DURING BUSINESS HOURS-SEE NOTE ON E.2 |