Permit: T10CM00176

Parcel: 131044000


Addresses:

4801 E 29TH ST #101

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) BLDG LOCKED AND NO ONE ON SITE
08/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE OPEN SPLICES OPEN BOXES AND UNSECURED LIGHT FIXTURES IN BACK AREA
2) NEED TO REVISE ONE LINE TO REFLECT HI/LEG SERVICE AND CHANGES IN FEEDERS FROM CU TO AL
3) NEED ACCESS TO ROOF
4) NEED SERVICE LABELING PER NEC 110.22
5) LABEL BREAKERS IN HOUSE PANEL AND PANEL 'C'
6) PLAN CALLS FOR EXHAUST FANS TO BE ON TIME CLOSCK SO FANS RUN DURING BUSINESS HOURS-SEE NOTE ON E.2