Permit: T10CM00166

Parcel: 114540460

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/03/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/01/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
YOU CANNOT USE THE AIR CONDITIONING CIRCUIT TO POWER THE SERVICE RECEPTACLE ON THE ROOF & YOU CANNOT USE THE GROUND TERMINAL IN PLACE OF THE REQUIRED NEUTRAL WIRE.