Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM00160

Parcel: 117120130


Addresses:

47 N SCOTT AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10CM00160

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2010 FIRE - FINAL Approved Approved 4/30/10
04/28/2010 FIRE - FINAL Denied Not approved 4/28/10
1.) Need address numbers for the building
2.) Need panic hardware for the rear exit door.( rear exit is through double doors and they open fully to 32 inchs each. OK to provide only one leaf of the double doors with panic hardware)
3.) Need an exit door or a passage way from patio area to a public way.
4.) The exit door for patio will require panic hardware.
5.) Need illuminated exit signs for all three exits doors.( main, double doors and patio door)
6.) Need emergency back-up lighting for both exits.
7.) Remove the keyed lock from the rear door.
8.) Must re-locate the manual pull station for the kitchen exhaust system. Minimum of 10 ft. from hazard.
9.) Can disregard items 2 thru 6 if the occupancy load is reduced to below 50 .