Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) PROVIDE MINIMUM 1/8" PER FT SLOPE ON ALL SECTIONS OF CONDENSATE DRAINS 2) PROVIDE GROMMETS AT LINE SET CONNECTIONS TO FAN COILS 3) WILL CHECK AT FINAL |
|
| 03/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND EXHAUST IN RESTROOMS OK TO COVER 2) PROVIDE BACKING AT CEILING BOXES PRIOR TO SHEETROCK 3) CONDENSATE DRAINS OK |