Permit: T10CM00124

Parcel: 12801007A


Addresses:

5510 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/21/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/16/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED 1ST LAYER OF FIRE WRAP - OK FOR 2ND LAYER
TERMINATE MINI SPLIT CONDENSATE INTO 3/4" WITH A FITTING.
NO FLEX DUCT WITHIN 18" OF TOP OF HOOD.
SHOW THAT T-BAR DIFFUSERS ARE PER PLAN
OK FOR CEILING TILES