Permit: T10CM00124

Parcel: 12801007A


Addresses:

5510 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10CM00124

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
07/14/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/09/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/02/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE PROOF OF LANDSCAPING BACKFLOW PROTECTION FOR WATER SUPPLY
2) SECURE MOP SINK FAUCET BRACKET
3) CAP ALL UNUSED PIPING
4) COMPLETE CORRECT LABELING AND INSTALL ACCESS PANELS
5) PROVIDE VACUUM RELIEF VALVE FOR ELEVATED WATER HEATER IN KITCHEN AREA
6) WASH AND RINSE AT 3-COMP SINK TO BE DIRECT DRAIN CONNECTION, INDIRECT DRAIN SANITIZE BOWL AT 3-COMP SINK
7) PROVIDE UPC LISTING FOR BACKFLOW PROTECTION FOR WATER ON ECOLAB APEX SYSTEMS IN KITCHEN WASH AREA OR PROOF OF CORRECT BACKFLOW PROTECTION
8) PROVIDE APPROVED WATER SUPPLY TUBING TO ECOLAB APEX SYSTEMS
9) REPAIR ALL LEAKS
10) INSTALL KITCHEN BOOSTER HEATER PER ? INSTALLATION INSTRUCTIONS ON IT
11) COMPLETE ALL EQUIPMENT INSTALLATIONS
12) EXPOSE CLEANOUT AT HAND SINK BY SODA DISPENSOR IN KITCHEN
13) INSTALL BACKFLOW PROTECTION FOR SOFTNER PER PLAN AND PIPE FOR APPROVED PLAN
14) HAVE ALL BACKFLOW CERTS ON SITE WITH STERILIZATION AND BACTERIA REPORT
15) PROVIDE BACKFLOW PROTECTION FOR NON CARBONATED WATER SUPPLY TO SODA SYSTEM
NOTE-VERIFY WITH SODA CONTRACTOR:
1) 1/2" BACKFLOW DEVICE WILL HANDLE FLOW REQUIRED TO (5) DISPENSOR AREAS