Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 06/24/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) INSPECTION TO ? SERIES RATING OF EQUIPMENT 2) INFORMATION PROVIDED BY ENGINEER OK, NEED LABELING PER NEC |
|
| 06/09/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK WIRING IN MILL WORK WALL 2) PROVIDE LETTER OF TORQUE FOR SERVICE GEAR 3) PROVIDE INFORMATION FOR SERVICE RATING, PLANS CALL FOR BREAKERS IN PANEL BOARDS TO BE 65K. NOTE ON PLANS CALLS FOR 3 TIER SYSTEM AT 65/22/10. WHAT IS TO BE RATED AT WHAT RATING 4) POST BOND TO HAVE POWER RELEASED |