Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | FIRE - FINAL | Approved | Approved 1/9/10. | |
| 02/03/2010 | FIRE - FINAL | Denied | Not approved 2/03/10 1.) Need the annual Fire Alarm inspection report. 2.) Need a sign over the main exit door that reads,"DOOR MUST REMAIN UNLOCKED WHEN THWE BUILDING IS OCCUPIED". 3.) Need a thumb-turn lock for the double doors. (east side) 4.) Remove the thumb-turn lock or the panic hardware from the designated secondary required exit door. (only one lock is allowed) 5.) Exterior doors in areas with more than a 49 occupany load must swing in the direction of egress travel. |