Permit: T10CM00089

Parcel: 11307085B


Addresses:

3061 N CAMPBELL AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
02/09/2010 FIRE - FINAL Approved Approved 1/9/10.
02/03/2010 FIRE - FINAL Denied Not approved 2/03/10
1.) Need the annual Fire Alarm inspection report.
2.) Need a sign over the main exit door that reads,"DOOR MUST REMAIN UNLOCKED WHEN THWE BUILDING IS OCCUPIED".
3.) Need a thumb-turn lock for the double doors. (east side)
4.) Remove the thumb-turn lock or the panic hardware from the designated secondary required exit door. (only one lock is allowed)
5.) Exterior doors in areas with more than a 49 occupany load must swing in the direction of egress travel.