Permit: T10CM00072

Parcel: 13308500A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/01/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) PROVIDE INSECT SCREENS AT COMBUSTION AIR LOUVER ON OUTSIDE WALL AND AT T-TOP ON ROOF
05/25/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TERMINATE CONDENSATE PER PLANS
2) THERE IS NO COMBUSTION AIR FOR FURNACES
3) PROVIDE AS REQUIRED BY CODE
4) ONE OPENING METHOD IS OK
05/21/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CONDENSATE DRAINS TERMINATED TO THE LAV. TAILPIECE IN EACH UNIT PER PLANS. USE PURPLE PRIMER ON ALL FITTINGS PRIOR TO GLUE
2 TERMINATE 3" E.F. DUCT 4" TERMINAL WITH A REDUCER FITTING
3) BE SURE ALL CEILING AND SIDEWALL REGISTER BOXES HAVE BACKING
4) SEAL ALL HOLES IN BOTTOM OF RETURN PLENIUMS WITH NON COMBUSTIBLE MATERIAL 2ND AND 3RD FLOORS