06/24/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/13/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE 2) PREVIOUS ITEMS CORRECTED |
|
01/05/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A/C DISCONNECT PER 440.14 2) RECEPT COVER 406.8 3) BONDING SERVICE NIPPLES 250.102 4) PLANS CALL FOR 3-4" FROM UTILITY 5) EXPOSE UNDERGROUND FOR INSPECTIONS 6) GROUNDING CONDUCTOR TO BE GREEN 250.119 7) NEED LETTER OF TORQUE |