Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10CM00069

Parcel: 20914001C


Addresses:

6155 S AVIATOR LN


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00069

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/13/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER OF TORQUE
2) PREVIOUS ITEMS CORRECTED
01/05/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) A/C DISCONNECT PER 440.14
2) RECEPT COVER 406.8
3) BONDING SERVICE NIPPLES 250.102
4) PLANS CALL FOR 3-4" FROM UTILITY
5) EXPOSE UNDERGROUND FOR INSPECTIONS
6) GROUNDING CONDUCTOR TO BE GREEN 250.119
7) NEED LETTER OF TORQUE