Permit: T10CM00028

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM00028

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/20/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/06/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE #2 FROM 06/24/10-MINIMUM SIZE VENT FOR WAER CLOSET IS 2 INCH MORE THAN 40' OF 2" HORIZONTAL VENT HAS BEEN INSTALLED
2) EXPOSE AND PROVIDE ACCESS TO SERVICE CONNECTION OVER HEAD TO VERIFY THAT IT IS ONE INCH
3) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE
06/25/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST DWV TO INITIAL PER PLAN
2) NOTE: IF VENTING RUNS OVER 40' HORIZONTAL IT SHALL BE INCREASED AND TESTED TO POINT OF CONNECTION TO EXISTING
3) IN WALL WATER PIPING TEST OK
4) 1" IS REQUIRED OVERHEAD PER PLAN AND INSULATION IS REQUIRED FOR PLAN