Permit: T10CM00027

Parcel: 133210550

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/30/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/28/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DO NOT USE FLEX COPPER ON A T & P DRAIN
2) PROVIDE MORE SLOPE ON HORIZONTAL SECTION OF DRAIN
3) WATER HEATER VENT CONNECTOR HAS A FITTIGN WITHOUT A CRIMPED MALE END
4) SEAL AROUND REFER LINE PENETRATION THRU EXTERIOR WALL
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT CONDENSOR
6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
7) TERMINATE T & P DRAIN COMPLETELY TO OUTDOORS WITH AN ELBOW ON END OF PIPE