Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00026
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECT ADDRESS LABEL |
|
03/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) A BOND WILL NEED TO BE POSTED FOR TEMP POWER 2) ALL DEVICES 8' AND BELOW TO BE INSTALLED 3) FILL ALL UNUSED OPENINGS AT PANEL 4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS 5) ONLY ONE CONDUCTOR PER LUG TERMINATION |
|
03/15/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HALLWAY AND PANEL AREA ABOVE CEILING |
|
03/08/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 2) NEED FIXTURE WHIP STUBS IN HARD LIDS |
|
03/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE APPROVED M/C STRAPS 2) STRAP M/C CABLE WITHIN 12" OF BOX 3) MISSING PLASTER RING 4) LOOSE FITTINGS 5) OK MANAGERS OFFICE |