Permit: T10CM00011

Parcel: 12510003G


Addresses:

3587 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM00011

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/09/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/07/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEWER HAS PRIVATE SEWER PERMIT, DO NOT DISCHARGE INTO SEWER UNTIL PCWWM AND PCDEQ APPROVES. DOES B.M. STILL HAVE TEST FITTING IN PLACE AT PUBLIC MAN HOLE ?
2) YARDWATER NOT INSTALLED PER PLAN, NO REDLINES AVAILABLE
3) WHO HAS INSPECTED PIPING FROM METER THRU BACKFLOW PREVENTERS FOR DOMESTIC AND IRRIGATION
4) PROVIDE STERILIZATION AND CLEAN BACTERIA REPORTS
5) VENTS TO BE PAINTED
6) VENTS WITHIN 10' OF AIR INTAKE TO BE EXTENDED
7) ALL OVER HARD PIPING TO BE SUPPORTED TO TABLE 3-2 2006 ?
8) GAS TEST GAUGES TO BE APPROVED TYPE 15 POUND GAUGE IN 1/10 INCREMENTS
9) THIS IS NOT A PUNCH LIST, THERE MAYBE ITEMS NOT ADDRESSED. THIS LIST SHOWS SOME OF THE REASONS YOU ARE NOT READY FOR A FINAL
05/10/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOF DRAIN WATER TEST OK
2) ADD OVER HEAD HANGERS AS REQUIRED
04/28/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL PIPING TO BE LAID ON A FIRM BASE, BRIDGING NOT PERMITTED
2) SOILS TO WET FOR LOCATION
3) EXPOSE ALL PIPE AND FITTINGS
4) TANK TO BE TESTED TO LID
5) REINSPECTED 1:00 PM, TANK TESTED OK
6) OK TO COVER INTERCEPTOR AND PIPING
04/27/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/23/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NOT READY FOR INSPECTION
04/13/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WALL HYDRANT CENTER NORTH INSIDE OF COLUMN TO BLDG INTERIOR TEST OK