Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/14/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR TILES UPER LEVEL X-RAY ROOM 2) OK FOR TILES ALL AREAS MECHANICAL ONLY, STILL NEED TO PROVIDE BEADED COLLARS |
|
| 05/13/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/11/2010 | MECHANICAL - ABOVE CEILING | Cancelled | CANCELLED PER CONTRACTOR MIKE #480-818-2263 | |
| 05/11/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CUSTOMER CANCELLED INSPECTION |
|
| 05/07/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE MINIMUM 2" BEADED COLLARS ON ALL FLEX DUCT CONNECTIONS 2) PAINT INSIDE OF RETURN GRILL FLAT BLACK 3) PROVIDE ENGINEERS APPROVAL FOR USE H.E. TAPS IN LIEU OF AIR SCOOPS 4) PROVIDE FULL 1 X RADIUS ON FLEX BENDS 5) S/A PINCHED IN BREAKROOM LOWER LEVEL 6) S/A LOWER LEVEL NOT CONNECTED X2 7) PROVIDE SEISMIC ON ALL GRILLS |