Permit: T10CM00008

Parcel: 12405142A


Addresses:

501 N PARK AV #110


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM00008

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/14/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR TILES UPER LEVEL X-RAY ROOM
2) OK FOR TILES ALL AREAS MECHANICAL ONLY, STILL NEED TO PROVIDE BEADED COLLARS
05/13/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
05/11/2010 MECHANICAL - ABOVE CEILING Cancelled CANCELLED PER CONTRACTOR MIKE #480-818-2263
05/11/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) CUSTOMER CANCELLED INSPECTION
05/07/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE MINIMUM 2" BEADED COLLARS ON ALL FLEX DUCT CONNECTIONS
2) PAINT INSIDE OF RETURN GRILL FLAT BLACK
3) PROVIDE ENGINEERS APPROVAL FOR USE H.E. TAPS IN LIEU OF AIR SCOOPS
4) PROVIDE FULL 1 X RADIUS ON FLEX BENDS
5) S/A PINCHED IN BREAKROOM LOWER LEVEL
6) S/A LOWER LEVEL NOT CONNECTED X2
7) PROVIDE SEISMIC ON ALL GRILLS