Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU01916
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2011 | FIRE - ALARM FINAL | Approved | ||
10/25/2011 | FIRE - ALARM FINAL | Denied | Placement and testing of core and T.I. plans approved. Testing for ground fault and missing battery, missing main power, missing phone line and phone line communications approved. All devices for core and T.I. plans came in properly. Still need to test all tampers and flow switches throughout building and fire pump room. Need to test pre-action system. | |
10/19/2011 | FIRE - ALARM FINAL | Not ready for Inspection | 1. Page FA2 Stair 4 or maybe 3? No horn/sounder need to install one. 2. Page FA3 Data center, add two more horns/sounders on north wall of the room. Room is to loud for the devices that are installed, need to be 10 dec. above room sounds during operations. 3. 1st floor drive ramp to 2nd floor drive strobes and sounders failed. 4. 5th floor short on sounder line showing on panel, strobe/sounder on wall to stair #1 5. 4th floor family restroom add strobe/sounder 6. 4th floor AOR's not wired to the outside switches. |