Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10BU01916

Parcel: 11717023E


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU01916

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2011 FIRE - ALARM FINAL Approved
10/25/2011 FIRE - ALARM FINAL Denied Placement and testing of core and T.I. plans approved. Testing for ground fault and missing battery, missing main power, missing phone line and phone line communications approved. All devices for core and T.I. plans came in properly. Still need to test all tampers and flow switches throughout building and fire pump room. Need to test pre-action system.
10/19/2011 FIRE - ALARM FINAL Not ready for Inspection 1. Page FA2 Stair 4 or maybe 3? No horn/sounder need to install one.
2. Page FA3 Data center, add two more horns/sounders on north wall of the room. Room is to loud for the devices that are installed, need to be 10 dec. above room sounds during operations.
3. 1st floor drive ramp to 2nd floor drive strobes and sounders failed.
4. 5th floor short on sounder line showing on panel, strobe/sounder on wall to stair #1
5. 4th floor family restroom add strobe/sounder
6. 4th floor AOR's not wired to the outside switches.