Inspection Status: Approved
Inspection History: FUEL TANK FINAL 791-4502
| Date |
Description |
Inspector |
Results |
Comments |
| 04/07/2011 |
FUEL TANK FINAL 791-4502 |
|
Approved |
Tank is approved for use |
| 03/22/2011 |
FUEL TANK FINAL 791-4502 |
|
Continued |
The system is operational. The overfill valves are still on order. |
| 03/15/2011 |
FUEL TANK FINAL 791-4502 |
|
Continued |
Pressure test on the piping passed, ground rod installed. Piping secured. Tank is ready for fuel. |
| 03/14/2011 |
FUEL TANK FINAL 791-4502 |
|
Continued |
Met with contractor and discussed the corections needed |
| 03/03/2011 |
FUEL TANK FINAL 791-4502 |
|
Not ready for Inspection |
Overfill protection needs to be operational, dispenser hose replaced and tank grounded. |