Permit: T10BU01893

Parcel: 12002233A


Addresses:

4445 S 15TH AV

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
02/09/2012 FIRE SPKLR - FINAL Approved
02/03/2012 FIRE SPKLR - FINAL Denied 1. SPRINKLER RISER NEEDS TO BE PAINTED AND INSULATED.
2.. CLOSET NEXT TO KITCHEN NEEDS TO HAVE HEAD MOVED AT LEAST FOUR INCHES OFF WALL.
3. CLOSET NEEDS HEAD ADDED SEE PLANS FOR DETAILS.
4. MANY ESCUSIONS MISSING.
5 SEVERAL HEADS HAVE TAPE ON THEM.
6. NEED AS BUILTS GARAGE IS NO LONGER A GARAGE. AND HEADS THAT ARE 175 DEGREE HEADS ARE NOW INSIDE LIVING AREA NEED TO BE CHANGED TO 155 DEGREE.