Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/11/2011 FIRE - ALARM FINAL Approved Approved 2/11/11 (see comment)
The manual pull station at front door exceeds minimum distance requirements. Current location is the only stable placement possible. Unstaller is to provide a readily visible sign above Pull Staion and also directional signs directing to it.
01/19/2011 FIRE - ALARM FINAL Denied Not approved 01/18/11
1.) Need to add or re-locate smoke detectors in order to provide proper coverage in the areas that were indicated on the walk. through inspection.
2.) Need to provide a minimum of 30 ft. seperation between smoke
detectors and a minimum of 15 feet seperation between detector an walls unless otherwise approved .
3.) The manual pull station located by the main exit doors must be re-located to meet code requirements.
01/07/2011 FIRE - ALARM FINAL Denied Not approved 1/7/11
1.) Need "AS BUILT" plans indicating changes from the original.
2.) Need "CUT SHEETS" refering to appliances.