Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2011 | FIRE - ALARM FINAL | Approved | Approved 2/11/11 (see comment) The manual pull station at front door exceeds minimum distance requirements. Current location is the only stable placement possible. Unstaller is to provide a readily visible sign above Pull Staion and also directional signs directing to it. |
|
| 01/19/2011 | FIRE - ALARM FINAL | Denied | Not approved 01/18/11 1.) Need to add or re-locate smoke detectors in order to provide proper coverage in the areas that were indicated on the walk. through inspection. 2.) Need to provide a minimum of 30 ft. seperation between smoke detectors and a minimum of 15 feet seperation between detector an walls unless otherwise approved . 3.) The manual pull station located by the main exit doors must be re-located to meet code requirements. |
|
| 01/07/2011 | FIRE - ALARM FINAL | Denied | Not approved 1/7/11 1.) Need "AS BUILT" plans indicating changes from the original. 2.) Need "CUT SHEETS" refering to appliances. |