Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10BU01663

Parcel: 125100740

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/12/2012 FIRE SPKLR - FINAL Approved
03/13/2012 FIRE SPKLR - FINAL Denied 1. Closet in bedroom #6 needs sprinkler coverage
2. Bedroom #9 on plans move sprinkle head away from wall more than 4 "
3. Add coverage in outside hot water heater room.
4. Add coverage in dinning room head to close to ceiling fan (blocked).
5. Need fire bell and monitoring system set up, must be an approved fire alarm system.
6. Need insulation on riser anything below 2" pipe needs to be covered.