Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2012 | FIRE SPKLR - FINAL | Approved | ||
| 03/13/2012 | FIRE SPKLR - FINAL | Denied | 1. Closet in bedroom #6 needs sprinkler coverage 2. Bedroom #9 on plans move sprinkle head away from wall more than 4 " 3. Add coverage in outside hot water heater room. 4. Add coverage in dinning room head to close to ceiling fan (blocked). 5. Need fire bell and monitoring system set up, must be an approved fire alarm system. 6. Need insulation on riser anything below 2" pipe needs to be covered. |