Inspection History: FIRE SPKLR - FINAL

Permit Number - T10BU01663

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2012 FIRE SPKLR - FINAL Approved
03/13/2012 FIRE SPKLR - FINAL Denied 1. Closet in bedroom #6 needs sprinkler coverage
2. Bedroom #9 on plans move sprinkle head away from wall more than 4 "
3. Add coverage in outside hot water heater room.
4. Add coverage in dinning room head to close to ceiling fan (blocked).
5. Need fire bell and monitoring system set up, must be an approved fire alarm system.
6. Need insulation on riser anything below 2" pipe needs to be covered.