Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/18/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*PROVIDE INTERLOCK BETWEEN TYPE I EXHAUST AND MAKE-UP AIR PROVIDE GAS TO HOOD FOR SMOKE CONTAINMENT TEST ALL OTHER ITEMS DATED 11/17/10 HAVE BEEN CORRECTED |
|
| 11/17/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) TYPE 1 GREASED DUCT IS LIQUID TIGHT WELDED CONSTRUCTION, IT APPEARS TO BE OF PROPER GAUGE, FIRE CHASE APPEARS TO BE OF APPROVED MANNER AT TIME OF ORIGINAL INSTALLATION. FANS ARE APPROVED FOR GREASE LADEN VAPORS. OK TO PROCEED 2) PROVIDE INTER LOCK BETWEEN EXHAUST AND M.V.A. 3) PROVIDE GREASE RECEPTORS AT FANS 4) PROVIDE HINGE KITS AT FANS WITH CHAIN STOPS 5) PROVIDE APPROVED WIRING TO FANS 6) PROVIDE GASKETS AT FAN TO DUCT CONNECTIONS |