Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T10BU01494
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2010 | FIRE - KITCHEN EXH HOOD FINAL | Approved | Approved 12/13/10 | |
12/09/2010 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Partial approval 12/9/10 1.) Hoods #3 and #4 tested and approved. 2.) Hood #1 not tested (electrical problem) 3.) Hood #2 make-up air did not shut down upon activation of system. 4.) Need to mount the "K" extinguishers. 5.) Need to lable the "pull station" for the #1 and the #2 systems 6.) Need to lable the location of the gas valves. |
|
12/07/2010 | FIRE - KITCHEN EXH HOOD FINAL | Not ready for Inspection |