Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2010 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 10/04/2010 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | ||
| 10/01/2010 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | IVRS - RI canceled | |
| 09/30/2010 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. No more than 12" from deck 2. Need coverage in exit ways 3. No more then 7' 6" off walls (holding cooler room south wall) 4. Need new calculations for remote area #2 5. Dry storage room heads no more 7' 6" off walls 6. Remove hose bib from riser 7. Finish install and do 200 PSI test for 2 hours |