Inspection History Details
Inspection Status: Approved
Inspection History: GRADING - TIER REV
Permit Number - T10BU01407
Inspection Description - GRADING - TIER REV
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2013 | GRADING - TIER REV | Approved | ||
11/02/2012 | GRADING - TIER REV | Continued | 1) CONTRACTOR INSTALLING UNDERGROUND RET/DET BASIN. SOME CHANGES ARE NEEDED TO THE ORIGINAL DESIGN IN ORDER TO INSTALL. 2) I NEED CONTACT FROM THE ENGINEER OF RECORD STATING THAT THE CHANGES MADE ARE ACCEPTABLE. 3) ANY AND ALL CHANGES MADE TO SITE/GRADING MUST BE SHOWN ON THE AS-BUILT DRAWING. 4) PRIOR TO FINAL APPROVAL , PROVIDE A CERTIFICATION STATEMENT FROM THE ENGINEER OF RECORD STATING THAT THE SITE/GRADING WAS COMPLETED PER THE APPROVED PLAN. 5) NO SIGNIFICANT STORM WATER CONCERNS AT THIS TIME. 6) ENSURE ALL MORTAR MIXING AND/OR CONCRETE MIXING DONE ON SITE IS CONTAINED AND CLEANED UP IF CONTAINMENT OVERFLOWS. |
|
08/24/2012 | GRADING - TIER REV | Continued | 1) APPROXIMATELY .5" OF RAIN IN LAST 24 JOURS ON SITE. 2) SEDIEMNT CONTROLS ARE IN PLACE ALONG THE PERIMETER IF THE SITE ALONG ALL DOWN SLOPES. 3) ALL SEDIEMNT CONTROLS APPEAR TO HAVE WORKED AND NO DISCHARGES ARE EVIDENT. 4) A NEW SEDIEMNT BASIN HAS BEEN CONSTRUCTED AND IS WORKING. 5) SITE IS IN COMPLIANCE W/ YOUR SWPPP, THE CITY OF TUCSON, AND ADEQ. 6) NO SITE WORK AT THIS TIME. ** NOTE: CHANGES TO PIPE GRADES ALONG SW CORNER OF SITE. REVIEW PLANS FOR DRY WELL APPROVAL AND STATE REGISTRATION REQ. LOOK AT COMPACTION RESULS FOR MANHOLE |