Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2010 | POOL/SPA ELECTRIC | Approved | ||
| 10/27/2010 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 10/05/2010 | POOL/SPA ELECTRIC | Denied | 1) NO FOOT HOLDS ALLOWED IN 5' FENCE AT POOL-CHECK EXISTING GATE AT REAR (GATE RAILS) 2) NEED TO SATISFY REQUIREMENT FOR ELEVATION CERT WITH S. GRREN 3) NEED TO BOND ALL METAL WITHIN 5' OF WATERS EDGE 4) SET PUMP MOTOR ON STABLE SURFACE NOT BLOCKS ? 5) FINISH BONDING ON ALL EQUIPMENT |
|
| 09/13/2010 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND CONDUIT OK |
|