Permit: T10BU01240

Parcel: 13403037B


Addresses:

8727 E 22ND ST #01

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/06/2010 FIRE - ALARM FINAL Approved
08/05/2010 FIRE - ALARM FINAL Not ready for Inspection Not ready 8/5/10
1.) Install manual pulls at each exit door.
2.) Remove non-reguired smoke alarms and heat detaectors. Provide cover plates
3.) Relocate smoke detector to 36 inches minimum away from air vent located in FCAP room.
4. Changes to be made, approved via telephone by FIre plans reviewer. "AS BUILT" plans to be forwarded.
5.) Lable date on batteries