Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2010 | FIRE - ALARM FINAL | Approved | ||
| 08/05/2010 | FIRE - ALARM FINAL | Not ready for Inspection | Not ready 8/5/10 1.) Install manual pulls at each exit door. 2.) Remove non-reguired smoke alarms and heat detaectors. Provide cover plates 3.) Relocate smoke detector to 36 inches minimum away from air vent located in FCAP room. 4. Changes to be made, approved via telephone by FIre plans reviewer. "AS BUILT" plans to be forwarded. 5.) Lable date on batteries |