Permit: T10BU01177

Parcel: 13101071F


Addresses:

2222 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/09/2010 FIRE - ALARM FINAL Approved
09/09/2010 FIRE - ALARM FINAL Not ready for Inspection Not ready 9/9/10
1.) Need door sweep
2.) Need door sealed
3.) Need room integrety test results (passing results)
4.) HVAC must shut down upon activation of system
5.) Systems testing was not performed. Must perform complete test
08/30/2010 FIRE - ALARM FINAL Cancelled
08/24/2010 FIRE - ALARM FINAL Cancelled
08/23/2010 FIRE - ALARM FINAL Cancelled IVRS - RI canceled