Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T10BU01140
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2011 | FIRE SPKLR - FINAL | Approved | ||
| 05/23/2011 | FIRE SPKLR - FINAL | Correction Required | 1. Problems found contractor and fire dept. made a list of problems such as; Add sprinkler coverage in closets in room 130 building "C" - add sprinkler cover in janitor closet room 137 building "C" ect. 2. Tested all flow and tamper switches all passed test was done on 05/19/2011. 3. Inspectors test valve is not needed if the flow switch is remove from the elevator rooms 4. Received paperwork on fire pump test, pump test done. |
|
| 05/02/2011 | FIRE SPKLR - FINAL | Partial Approval | Fire pump test done and passed, waiting for print out Need to weather proof holes on top of fire control box for fire pump. |