| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2011 | FIRE SPKLR - OH PIPING & HYDRO | Approved | Fire pump piping and test header 200 PSI for 2 hours approved Sprinkler head was added in lobby. |
|
| 04/21/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | CORRECT SPRINKLER COVERAGE IN LOBBY BUILDING "B" SOUTHWEST END. REMOVE CAP FROM SPRINKLER HEAD IN ELECT. ROOM WHERE TEMP FACP PANEL IS. |
|
| 03/21/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 6'' Main fire loop tested for 2 hours at 200 psi | |
| 02/23/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | partail building a/standpipe | |
| 02/23/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | partial first floor building c | |
| 02/10/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | STANDPIPE/#1 STAIRWAY | |
| 02/02/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | A Building 1st Floor | |
| 01/28/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Building B 1st Floor | |
| 12/16/2010 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | PARTIAL - BUILDING A FLOORS 2,3,4 | |
| 10/13/2010 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | PARTIAL - BUILDING B FLOORS 2,3,4 | |
| 10/13/2010 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | PARTIAL - BUILDING B FLOORS 2,3,4 | |
| 09/22/2010 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 5th and 6th floors "C" building Building B standpipe press test |
|
| 09/07/2010 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | BUILDING "C" 2ND - 3RD - 4TH FLOORS |