Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2010 | FIRE - KITCHEN EXH HOOD FINAL | Approved | Approved 8/31/10 A fire alarm system was interlocked with the burglury alarm. The panel was not U/L listed for both fire and burglury. Instructed to DC fire alarm system Also instructed owner to submit plans and obtain permit when installing proper panel. |
|
| 08/30/2010 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Need plans and permit for the back hood system we have nothing on file or in the system. 2. Need as bults for the front hood system lots of changes have been made like the following: plans show two salamanders 30 inches long - but what is on site is one 14 x 45 inch, plans shows 4 burner range but on site is a 8 burner range with back shelf added to the wall, plans show 3 stock pots - on site 2 fryers 18 x 24 and a pressure cooker 18 inch. 3. Correct coverage over 8 burner stove with shelf add over range nozzles are at 41 inched above, according to book should be set at 24 - 35 inches. 4. Need to check coverage for salamander size is 14 x 45 inches below the requirement for square inches but again according to the book the longest size is 36 inches therefore over 9 inches. Need to add another nozzle to the salamander, but watch out you will be over your points for the bottle. |
|
| 08/27/2010 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | Cancelled 8/27/10 | |
| 06/18/2010 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | Cancelled 6/18/10 |