Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FUEL TANK FINAL 791-4502
| Date |
Description |
Inspector |
Results |
Comments |
| 06/29/2010 |
FUEL TANK FINAL 791-4502 |
|
Approved |
Approved for use |
| 06/28/2010 |
FUEL TANK FINAL 791-4502 |
|
Not ready for Inspection |
|
| 06/24/2010 |
FUEL TANK FINAL 791-4502 |
|
Continued |
Piping passed pressure test. Approved to backfill. |