Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2010 | FIRE - ALARM FINAL | Approved | RAN 7 MIN. TIME ON SOUNDERS - PASS DID THE FOLLWING; TAKING WIRING APART AT LOOPS TESTED BOTH SIDES - PASS TESTED 10 PERCENT OF SMOKES TESTED 2 PULL STATIONS TESTED 1 HEAT DECT. |
|
| 07/27/2010 | FIRE - ALARM FINAL | Not ready for Inspection | TURN OFF A/C POWER AT 1034AM FOR 24 HOUR STAND BY TEST |