Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10BU00789

Parcel: 13316030E

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00789

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 FIRE - ALARM FINAL Approved AS BUILTS MATCHED
02/10/2010 FIRE - ALARM FINAL Partial Approval approved 2/10/10.
1.) This is a none required system. Items
#1, #2 are disregarded.
2.) Item #3 also disregarded. Per code,
this particular layout allows for 42 ft.
seperation between smoke detectors.
3.) "AS BUILT" plans will be forwarded.
01/22/2010 FIRE - ALARM FINAL Denied Not approved 1/22/10
Corrected address 6369 E. Tanke Verde Rd.
1.) All signals recieved by central monitoring station are "Trouble" signals only. No "alarm" signals recievied.
2.) Each building must carry it's own individual address ID signal. Currently, central alarm is recieving the same address ID signal for all three buildings.
3.)The distance of the smoke detector located in the middle of the hallway on both floors is beyond the maximum distance allowed. (30 feet)
4.) Duct detector in suite # 170 did not initiate alarm when activated and did not shut down the air flow.