Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00789
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2010 | FIRE - ALARM FINAL | Approved | AS BUILTS MATCHED | |
02/10/2010 | FIRE - ALARM FINAL | Partial Approval | approved 2/10/10. 1.) This is a none required system. Items #1, #2 are disregarded. 2.) Item #3 also disregarded. Per code, this particular layout allows for 42 ft. seperation between smoke detectors. 3.) "AS BUILT" plans will be forwarded. |
|
01/22/2010 | FIRE - ALARM FINAL | Denied | Not approved 1/22/10 Corrected address 6369 E. Tanke Verde Rd. 1.) All signals recieved by central monitoring station are "Trouble" signals only. No "alarm" signals recievied. 2.) Each building must carry it's own individual address ID signal. Currently, central alarm is recieving the same address ID signal for all three buildings. 3.)The distance of the smoke detector located in the middle of the hallway on both floors is beyond the maximum distance allowed. (30 feet) 4.) Duct detector in suite # 170 did not initiate alarm when activated and did not shut down the air flow. |