Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00787
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2010 | FIRE - ALARM FINAL | Approved | AS BUILTS PLANS MATCHED | |
02/10/2010 | FIRE - ALARM FINAL | Partial Approval | Approved 2/10/10. 1.) This is a none required system. Items #1, #2 are disregarded. 2.) Item #3 also disregarded. Per code, this particular layout allows for 42 ft. seperation between smoke detectors. 3.) "AS BUILT" plans will be forwarded. |
|
01/22/2010 | FIRE - ALARM FINAL | Denied | 1. All signals recieved by central monitoring station are "trouble signals" only, no "alarm" signals recieved. 2. Each building must carry it's own idividual ID address singal. Currently, central alarm is recieving same address signal for all three buildings. 3. Duct detector in suite #110 did not initiate alarms signal when activated and did not shut down air flow. 4. Distance of smoke detector located in the center of the hallway in all floors are beyond max. distance allowed. (30 feet) |