Permit: T10BU00787

Parcel: 13316030E

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00787

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 FIRE - ALARM FINAL Approved AS BUILTS PLANS MATCHED
02/10/2010 FIRE - ALARM FINAL Partial Approval Approved 2/10/10.
1.) This is a none required system. Items
#1, #2 are disregarded.
2.) Item #3 also disregarded. Per code,
this particular layout allows for 42 ft.
seperation between smoke detectors.
3.) "AS BUILT" plans will be forwarded.
01/22/2010 FIRE - ALARM FINAL Denied 1. All signals recieved by central monitoring station are "trouble signals" only, no "alarm" signals recieved.
2. Each building must carry it's own idividual ID address singal. Currently, central alarm is recieving same address signal for all three buildings.
3. Duct detector in suite #110 did not initiate alarms signal when activated and did not shut down air flow.
4. Distance of smoke detector located in the center of the hallway in all floors are beyond max. distance allowed. (30 feet)