Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00786
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2010 | FIRE - ALARM FINAL | Approved | AS BUILTS MATCHED | |
02/10/2010 | FIRE - ALARM FINAL | Partial Approval | approved 2/10/10. 1.) This is a none required system. Items #1, #2 are disregarded. 2.) Item #3 also disregarded. Per code, this particular layout allows for 42 ft. seperation between smoke detectors. 3.) "AS BUILT" plans will be forwarded. |
|
01/22/2010 | FIRE - ALARM FINAL | Denied | Not approved 1/22/10 1.) All signals recieved by central monitoring station are "trouble" signals only. No "alarm" signals recieved. 2.) Each building must carry it's own idividual ID signal. Currently, central alarm is recieving the same address ID signal for all three buildings. 3.) The distance of the smoke detector located in the middle of the hallway in the second floor is beyond the maximum distance allowed. (30 feet) 4.) Need an "AS BUILT" plan for the first floor. |