Permit: T10BU00786

Parcel: 13316030E

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00786

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 FIRE - ALARM FINAL Approved AS BUILTS MATCHED
02/10/2010 FIRE - ALARM FINAL Partial Approval approved 2/10/10.
1.) This is a none required system. Items
#1, #2 are disregarded.
2.) Item #3 also disregarded. Per code,
this particular layout allows for 42 ft.
seperation between smoke detectors.
3.) "AS BUILT" plans will be forwarded.
01/22/2010 FIRE - ALARM FINAL Denied Not approved 1/22/10
1.) All signals recieved by central monitoring station are "trouble" signals only. No "alarm" signals recieved.
2.) Each building must carry it's own idividual ID signal. Currently, central alarm is recieving the same address ID signal for all three buildings.
3.) The distance of the smoke detector located in the middle of the hallway in the second floor is beyond the maximum distance allowed. (30 feet)
4.) Need an "AS BUILT" plan for the first floor.