Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00647
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2011 | FIRE - ALARM FINAL | Approved | ||
05/05/2011 | FIRE - ALARM FINAL | Partial Approval | Building "A" 1. Label M3-70 heat and M3-71 in room A122 trash and recycling 2. Change outside A/V by room A111 faculty service 31:S3-1B need 75 cd and a sounder. 2ND FLOOR NO PROBLEMS 3RD FLOOR NO PROBLEMS 4TH FLOOR NO PROBLEMS 5TH FLOOR NO PROBLEMS 6TH FLOOR NO PROBLEMS |
|
05/04/2011 | FIRE - ALARM FINAL | Partial Approval | Did Building "B" 1st Floor Outside strobes and horns failed no sound and not weather proof. Secure flex wire in mechanical room to duct detector M1-166 2nd floor Room B207 no sounder Between rooms B226 and B225 remount A/V and install weather proof type. 3rd floor Room B302 no sounder failed Room B309 no sounder failed Room B319 no sounder failed By bathroom B301 in hallway no sounder 42:S2-2 4th floor no problems 5th floor no problems Roof top no problems |
|
05/03/2011 | FIRE - ALARM FINAL | Denied | Did building "B" Rooms B402 & B518 sounders failed -REPAIRED While testing system horns and storbes failed at room B516 we stopped and then went to 4th floor. - REPIRED On 4th floor all strobes and horns failed system failed to work. - REPAIRED |
|
05/02/2011 | FIRE - ALARM FINAL | Partial Approval | Tamper failed 4th floor building "E" - REPAIRED Tamper and flow switch failed 2nd floor building "B" - REPAIRED Tamper and flow switch failed 3rd floor building "B" - REPAIRED Tamper and flow switch failed 4th floor building "B" - REPAIRED |
|
04/29/2011 | FIRE - ALARM FINAL | Denied | Building 'C' 1. Electrical cover plates required on fire alarm boxes in C101,C103 and various locations. 2. Add DD to as-builds C128 'Great Room Storage' 3. Remove excess conduit in C105. 4. Calk penetration holes in C105, C103 and C312 (by duct on East side). 5. Label SD C415 (Elec Closet). 6. SD to close to exhaust fan on floors 2 and 4. |
|
04/28/2011 | FIRE - ALARM FINAL | Denied | Did building "D" the following need to be corrected: Dress out test switches for duct detector on roof - DONE 1st room D114A IDA need to move smoke 3 feet away from intake or exhaust grills - DONE Floor 2, 3, 4 & 5 are done no problems NOTE: The following problems fixed on building "E" Smoke was relocated and works in room E113A Sounders replaced and work in rooms E114 and E108 Dampers on 3rd floor REPAIRED |
|
04/27/2011 | FIRE - ALARM FINAL | Denied | Did final alarm test on Building "E" 1st thru 4 and roof, need to repair the following: 1st floor Relocate smoke 3 feet away from intake or exhaust grills, room E113A IDA. - REPAIRED Sounders failed to work in rooms E114 accessible double room and E108 double room. - REPAIRED 3rd floor Dampers failed to shut down a/c unit. - REPAIRED Battery cabinet to nacs does not lock. - DONE 2nd floor done no problems 4th floor done no problems Roof done no problems |