Permit: T10BU00647

Parcel: 124051320


Addresses:

515 N TYNDALL AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00647

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2011 FIRE - ALARM FINAL Approved
05/05/2011 FIRE - ALARM FINAL Partial Approval Building "A"
1. Label M3-70 heat and M3-71 in room A122 trash and recycling
2. Change outside A/V by room A111 faculty service 31:S3-1B need 75 cd and a sounder.
2ND FLOOR NO PROBLEMS
3RD FLOOR NO PROBLEMS
4TH FLOOR NO PROBLEMS
5TH FLOOR NO PROBLEMS
6TH FLOOR NO PROBLEMS
05/04/2011 FIRE - ALARM FINAL Partial Approval Did Building "B"
1st Floor
Outside strobes and horns failed no sound and not weather proof.
Secure flex wire in mechanical room to duct detector M1-166
2nd floor
Room B207 no sounder
Between rooms B226 and B225 remount A/V and install weather proof type.
3rd floor
Room B302 no sounder failed
Room B309 no sounder failed
Room B319 no sounder failed
By bathroom B301 in hallway no sounder 42:S2-2
4th floor no problems
5th floor no problems
Roof top no problems
05/03/2011 FIRE - ALARM FINAL Denied Did building "B"
Rooms B402 & B518 sounders failed -REPAIRED
While testing system horns and storbes failed at room B516 we stopped and then went to 4th floor. - REPIRED
On 4th floor all strobes and horns failed system failed to work. - REPAIRED
05/02/2011 FIRE - ALARM FINAL Partial Approval Tamper failed 4th floor building "E" - REPAIRED
Tamper and flow switch failed 2nd floor building "B" - REPAIRED
Tamper and flow switch failed 3rd floor building "B" - REPAIRED
Tamper and flow switch failed 4th floor building "B" - REPAIRED
04/29/2011 FIRE - ALARM FINAL Denied Building 'C'
1. Electrical cover plates required on fire alarm boxes in C101,C103 and various locations.
2. Add DD to as-builds C128 'Great Room Storage'
3. Remove excess conduit in C105.
4. Calk penetration holes in C105, C103 and C312 (by duct on East side).
5. Label SD C415 (Elec Closet).
6. SD to close to exhaust fan on floors 2 and 4.
04/28/2011 FIRE - ALARM FINAL Denied Did building "D" the following need to be corrected:
Dress out test switches for duct detector on roof - DONE
1st room D114A IDA need to move smoke 3 feet away from intake or exhaust grills - DONE
Floor 2, 3, 4 & 5 are done no problems
NOTE: The following problems fixed on building "E"
Smoke was relocated and works in room E113A
Sounders replaced and work in rooms E114 and E108
Dampers on 3rd floor REPAIRED
04/27/2011 FIRE - ALARM FINAL Denied Did final alarm test on Building "E" 1st thru 4 and roof, need to repair the following:
1st floor
Relocate smoke 3 feet away from intake or exhaust grills, room E113A IDA. - REPAIRED
Sounders failed to work in rooms E114 accessible double room and E108 double room. - REPAIRED
3rd floor
Dampers failed to shut down a/c unit. - REPAIRED
Battery cabinet to nacs does not lock. - DONE
2nd floor done no problems
4th floor done no problems
Roof done no problems