Permit: T10BU00570

Parcel: 124051320


Addresses:

515 N TYNDALL AV


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T10BU00570

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2011 FIRE SPKLR - FINAL Approved
05/10/2011 FIRE SPKLR - FINAL Correction Required Walk through done of all buildings some problems found a list was made re-inspection needed for repairs on list.
05/05/2011 FIRE SPKLR - FINAL Partial Approval Building "A"
Correct sprinkler coverage in Great room A121, south east ceciling pocket.
Correct sprinkler coverage in trash and recycling room A122, north wall.
Correct sprinkler coverage in mechanical room A114, duct work over 4' need coverage under and a sprinkler head blocked by piping south wall.
Need to install inspectors test valve in elevator rooms for flow switches
Need to paint and insulate sprinkler piping to elevator rooms or change piping to 2" or bigger to protect from freezing - DONE
05/02/2011 FIRE SPKLR - FINAL Not ready for Inspection 1. Add sprinkler coverage in closet front lobby building B-1. DONE
2. Tamper failed 4th floor building "E" - REPAIRED
3. Tamper and flow switch failed 2nd floor building "B" - REPAIRED
4. Tamper and flow switch failed 3rd floor building "B" - REPAIRED
5. Tamper and flow switch failed 4th floor building "B" - REPAIRED
6. Need to do 200 psi test on standpipe system building "B". DONE
7. Need to correct sprinkler coverage in tunnels both southwest and northwest exit ways. DONE
05/02/2011 FIRE SPKLR - FINAL Not ready for Inspection Pump test done passed waiting for print out - DONE have print out
03/22/2011 FIRE SPKLR - FINAL Not ready for Inspection electrical not complete could not test fire pump.