Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00444
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2010 | FIRE - ALARM FINAL | Approved | Approved 6/8/10 | |
06/02/2010 | FIRE - ALARM FINAL | Denied | Not approved 6/2/10 1.) Heat detaector too close to light fixture. Storage closet, 1st.floor 2.) Smoke detectors too far from wall. Office # 207. 2nd floor. 3.) Need to add 3 smokes in mechanical room. 4.) Wil need lock for dedicated fire alarm breaker. |