Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00388

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2010 FIRE - ALARM FINAL Approved Approved
04/05/2010 FIRE - ALARM FINAL Partial Approval 1. Minimum battery size required 9.920 AH.
2. 120V residential smoke detector interconnected (TYP) required in great room.
3. No smoke detector in library as per plans.
4.AC fault not picked up by monitoring station.