Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00245
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2010 | FIRE - ALARM FINAL | Approved | Approved 6/30/10 | |
06/10/2010 | FIRE - ALARM FINAL | Denied | Not approved 6/9/10 1.) Appliances tested and checked for proper location 2.) Alarm signals reported to the FACP but did not report to central alarm 3.) Only signals repotring to central alarm were water flow and tamper alarm 4.) Water gong did not sound off |