Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T10BU00177
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2011 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
09/14/2010 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Not approved 9/14/10 1.) Exhaust fan must remain running upon activation of system. |
|
08/26/2010 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | Cancelled 8/26/10 Problem with the electrical |
|
08/09/2010 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Not approved 8/9/10 1.) The exhaust fan shut down upon activation of the system. must remain running. 2.) The nozzle caps for the plenum and duct area blew off on activation, the nozzle caps for the appliances did not. |
|
08/06/2010 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | IVRS - RI canceled | |
05/05/2010 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Not approved 5/5/10 1.) Need mechanical final 2.) Exhaust fans on on the right side of system not operating properly. 3.) Make-up air not working . 4.) Gas and electrical power shut-off, OK 5.) Alarm system OK. 6.) Will re-test all other functions. |